The 12kV vacuum circuit breaker manufactured by DAHU ELECTRIC is the indoor switchgear with rated voltage up to 40.5kV,three phase AC 50/60Hz.It acts as the electrical protective and control device in the power system,especially applicable to locations that need frequent operating in rated current or under repeatedly on/off short circuit current.
This breaker was designed as a unit which gathering actuator and circuit breaker main body.It can be used for fixed mounting unit,also can be constituted as a withdrawable unit through outfit dedicated advancing mechanism.Corresponding interlock can be increased to meet the needs of XGN2,GG1A and other fixed cabinets.Simultaneously,it can coordinate with the KYN28A-12(GZS1) middle-arranged manual-driven switchgear,KYN61-40.5 floor standing switchgear or XGN-fixed switchgear as well.
Modular Mechanism
Modular mechanism design, highly standardized structure;
Mechanism is easy to assemble / disassemble and easy to maintain;
High reliability with less number of parts
Integrated charging handle, makes operation convenient and easy
Pot-type Pole
Environment friendly insulating material, PA66 provides light weight, high dielectric performance;
Recyclable and easy disposal after product life cycle;
Cost effective and reliable;
Vacuum Circuit Breaker
Fully meets the requirements of IEC and GB standards;
Complete interlocking, prevent misoperation, and provide safety in operation;
Modular design, shortened delivery time;
Small opening rebound and excellent performance;
Model explanation
VS1 - Product code
12 - 12KV
T - Spring Mechanism; M - Permanent Magnetic Mechanism
630 - 630A
25 - 25kA
W - Withdrawable type; F - Fixed type
150 - 150mm pole distance; 210 - 210mm pole distance; 1000 - 1000mm/1m pole distance
P - Potted type; E - Encapsulted type
Performance Advantage
The product is equipped with a bistable permanent magnet operating mechanism, the mechanism is equipped with a permanent magnet, by the permanent magnet to provide a holding force, so that the switch is maintained in the open and closed state, compared with the conventional spring operating mechanism, the number of mechanical parts is reduced, the mechanical transmission chain is shortened, so that the reliability of the switch is greatly improved, the mechanical life is greatly increased.
Item |
Unit |
Data |
Rated voltage |
kV |
12 |
Rated frequency |
Hz |
50 |
Rated insulation level 1 min power frequency withstand voltage pole to earth |
kV |
42 |
Rated insulation level 1 min power frequency withstand voltage phase |
kV |
48 |
Rated insulation level lightning impulse withstand voltage pole to earth |
kV |
75 |
Rated insulation level lightning impulse withstand voltage phase |
kV |
85 |
Power frequency withstand voltage of secondary circuit |
V |
2000 |
Rated current |
A |
630,1250, 1600, 2000, 2500, 3150, 4000, 5000 |
Rated short-circuit breaking current |
kA |
20, 25, 31.5, 40, 50 |
Rated short-time withstand current |
kA |
20, 25, 31.5, 40, 50 |
Rated short circuit duration |
s |
4 |
Rated peak withstand current |
kA |
50, 63, 80, 100, 125 |
Rated short-circuit making current |
kA |
50, 63, 80, 100, 125 |
Rated short circuit current breaking times (class E2) |
times |
30 |
Rated single/back to back capacitor bank breaking current |
A |
630/400, 800/400 |
Clearance between open contacts |
mm |
11±1 |
Contact stroke |
mm |
3~4 |
Allowable wear thickness of contact |
mm |
3 |
Average opening speed |
m/s |
0.9~1.4 |
Average closing speed |
m/s |
0.5~1.0 |
Contact closing bounce time |
ms |
≤2 |
Different phases of contact closing and opening |
ms |
≤2 |
Rebound amplitude of opening contact |
mm |
≤2 |
Opening time (rated voltage) |
ms |
20~50 |
Closing time (rated voltage) |
ms |
30~70 |
Mechanical life (M2) |
ms |
10,000(20,000) |
Rated operating voltage |
V |
AC110/220 DC110/220 |
Rated operation sequence |
|
O-0-CO-180s-CO |